○Barrier sealing hazardous area conduit fitting, suitable for unarmoured cables in flexible conduit

○Compliant with Ex eb, Ex db, and Ex tb safety standards

○Suitable for use in Group II and III Hazardous areas

○The gland provides a flameproof compound seal around the individual cable cores, making this suitable for cables which exhibit "cold flow" characteristics

○The Centaurus Conduit also provides an IP and cable retention seal on the outer jacket

○Certified to ATEX and IECEx standards with additional global approvals available (see technical for full list)

○Other threadforms available on request.

Specifications

Cable ØTLSWOuter Ø 'd'Conduit SizeThread Size "M"Max. No. of CoresMax. Over Core ØMin. Required CompoundArticle No.BIMED Code3D FileDatasheet
3,0 - 8,51625/25/26293/8"M20x1,599.57—KBCTNLS1XSM—PDF
6,0 -13,01630/30/26333/8"M20x1,599.57—KBCTNLS1SM—PDF
8,0 - 15,01625/29/2932.71/2"M20x1,599.57—KBCTNLS1M—PDF
8,0 - 15,01630/33/35393/4"M25x1,599.57—KBCTNLS2SM—PDF
13,5 - 21,01630/30/29331/2"M20x1,511129—KBCTNLS1LM—PDF
13,5 - 21,01630/33/35393/4"M25x1,511129—KBCTNLS2M—PDF
18,0 - 27,01640/40/3544.53/4"M25x1,5221520—KBCTNLS2LM—PDF
18,0 - 27,01640/43/45501"M32x1,5221520—KBCTNLS3M—PDF
23,0 - 33,01643/43/45501"M32x1,53621.531—KBCTNLS3LM—PDF
23,0 - 33,01645/52/54601 1/4"M40x1,53621.531—KBCTNLS4SM—PDF
29,0 - 40,01650/52/54601 1/4"M40x1,5552960—KBCTNLS4M—PDF
29,0 - 40,01655/60/6369.31 1/2"M50x1,5552960—KBCTNLS5SM—PDF
35,0 - 48,01658/63/6369.31 1/2"M50x1,5753790—KBCTNLS5M—PDF